Functional Test of the following:

As part of the initial commissioning of any new system, at minimum it shall be required by local, state and national Code to test the following:
-
Operation of the Control Unit including lamps, LEDs, LCD’s and fuses.
-
Alarming of each smoke detector by introducing smoke into the chamber of the detector.
-
Activation of each fire alarm pull box, manual pull station or manual release station.
-
Trouble annunciation from supervised circuits such as SLC (Signal Line Circuit).
-
Verification of off-site monitoring communication within the prescribed time limit.
-
Operation of keyed by-pass switches, maintenance switches and abort stations.
-
Fully loaded audio visual annunciation test for minimum prescribed time limit.
-
Verification of interlocks such as control shutdowns, fan pressurization activation, damper closures, etc…
-
Pressure testing of suppression pipe network for prescribed time limit.
-
Room pressurization testing for prescribed time limit.