fire alarm, detection, suppression
Follow Us:
 
Home
Contact Us
NetSITE Login
Loading

Commissioning a System

Functional Test of the following:

As part of the initial commissioning of any new system, at minimum it shall be required  by local, state and national Code to test the following:

  • Operation of the Control Unit including lamps, LEDs, LCD’s and fuses.
  • Alarming of each smoke detector by introducing smoke into the chamber of the detector.
  • Activation of each fire alarm pull box, manual pull station or manual release station.
  • Trouble annunciation from supervised  circuits such as SLC (Signal Line Circuit).
  • Verification of off-site monitoring communication within the prescribed time limit.
  • Operation of keyed by-pass switches, maintenance switches and abort stations.
  • Fully loaded  audio visual annunciation test for minimum prescribed time limit.
  • Verification of interlocks such as control shutdowns, fan pressurization activation, damper closures, etc…
  • Pressure testing of suppression pipe network for prescribed time limit.
  • Room pressurization testing for prescribed time limit.

Have A Question or Need More Help...

 

Atlanta, GA | Bloomington, IL | Bridgewater, NJ | Chicago, IL | Cincinnati, OH | Raleigh - Durham, NC | Indianapolis, IN | Los Angeles, CA | Kansas City, MO | Las Vegas, NV | Louisville, KY | San Francisco, CA | St. Louis, MO | Tampa, FL | Battle Creek, MI | Brooklyn, NY | Cherry Hill, NJ | Columbus, OH | Dallas, TX | Fayetteville, NC | Ft. Lauderdale, FL | Ft. Meyers, FL | Ft. Walton Beach, FL | Jacksonville, FL | Lafayette, LA | Morristown, TN | Nashville, TN | Newport, NC | New York, NY | Orlando, FL | Pittsburgh, PA | Tallahassee, FL
Copyright © 2009 www.orrprotection.com