Fike MicroMist Fire Suppression System

 

The Fike MicroMist system is a self contained,single fluid, pre-engineered water mist fire suppression system for total compartment protection of machinery spaces and compartmentalized gas turbine generators. The MicroMist system employs a brass nozzle which has demonstrated excellent performance extinguishing flammable liquid (Class B) fire scenarios. Each nozzle flows approximately 2.1 gallons/minute (8 liters/min) of water at 310 psi (21 Bar).  A single Fike MicroMist system is capable of protecting areas up to 9175 ft3 (260 m3), with a maximum ceiling height of 16’ (4.9m).


The MicroMist system is offered in 70 and 112 gallon (267 and 423 liter) configurations.  Each system package is skid mounted and includes all necessary valves and actuation components for system operation.  System nozzles are ordered separately.  Each MicroMist system package is pre-assembled and tested to ensure system reliability and simplify ease of installation.


Operating Principles

 

Water is an outstanding fire suppression agent due to its high heat capacity and latent heat of vaporization.  The Fike Micromist system nozzle uses a plate to slice the small jets of water that flow through the nozzle orifice.  The resulting water mist contains a variety of droplet sizes. The larger droplets produced by the nozzle provide the necessary energy and momentum to carry the smaller droplets to the base of the fire where the mist vaporizes and extinguishes the fire.  The simple theory behind this development is that a large amount of small droplets have a greater surface area than the same volume of large droplets, therefore absorb more heat.
 
Water mist systems extinguish fires using the following basic principles:

  • Cooling - As the mist is converted into vapor it removes heat from the fire source.
  • Inerting - As the water mist turns to steam it expands approximately 1700 times, forcing oxygen away from the flame front, thus denying it the oxygen necessary to support combustion. (localize inert environment)
  • Wetting - Primarily for incidental Class A fires; wetting of the surface helps extinguish the fire as well as contain it.


System Operation


When a fire condition is detected in a given protected hazard, the Fike control panel sends a signal to the releasing module to operate the Micromist suppression system. The water storage container is not under pressure until the system is actuated.  The water container utilizes a 3/4” (20mm) brass valve to control the flow of water to the system nozzles. The water container has a drain/fill valve and a vent valve to drain the water when necessary. A safety disc is also fitted on the water container which ruptures if the pressure inside reaches a pressure greater than 500 psi (34 bar).
 
The Micromist system contains nitrogen cylinder(s) and a water cylinder. The nitrogen storage cylinder provides pressure to drive the water to the system nozzles. When the system is operated, valves on the nitrogen tanks open and the resulting air pressure flows through a pressure regulating valve (PRV) which regulates the pressure to 320 psi (22 Bar). This pressure drives the water through the opened water valve and to the system nozzles. The Micromist system uses relatively short pulses of water, called cycling, to aid in the extinguishment of fires as well as minimize the property damage associated with a continuous discharge.

 


System Components


The Micromist suppression system comes pre-packaged on a skid produced from 3/8” (9.5mm) thick steel plate. The water cylinder is bolted to the skid and the nitrogen cylinder(s) are mounted to the water cylinder with straps. The skid is designed so it can be easily transported with a fork lift.  

The Fike Micromist system package is offered in 70 and 112 gallon (267 and 423 liter) configurations.  The 70 gallon system consists primarily of one nitrogen cylinder and a water storage container. The 112 gallon system has two nitrogen cylinders and one water storage container.  The nitrogen cylinders are charged to 1850 psi (128 bar) and fitted with a forged brass valve that is actuated with a solenoid valve.  The solenoid valve is fitted with a pressure gauge (or optional switch) so the pressure inside the cylinder can be monitored.

The piping requirements for the Micromist system offer the flexibility of copper tubing type K or L, stainless steel tubing or pipe as specified in NFPA 750. Due to the low flow requirements of the Micromist nozzle it is not mandatory that the piping be balanced, which improves system flexibility. Consult the Micromist Design, Installation, and Maintenance Manual (P/N 06-153) for detailed piping limitations.

The Micromist system nozzles are constructed of brass and contain a nozzle screen to trap any debris that might be in the system piping. The nozzle utilizes a 1/2” (15mm) NPT port to connect to the piping network.

 


Applications

 

Micromist systems are designed and have been tested for use in protecting flammable liquid (Class B) processes and incidental combustible (Class A) materials.

The Fike Micromist system has successfully passed the Factory Mutual fire test protocol for machinery spaces, and compartmentalized gas turbine generators. The system will effectively extinguish flammable liquid pool fires as well as spray fires which could ignite from a ruptured hose or pipe in a process using flammable liquids. Micromist applications include, but are not limited to, the following:

    • Compartmentalized gas turbine generators
    • Engine test cells
    • Generator rooms
    • Machinery spaces with incidental storage of
       flammable liquids
    • Oil pumps
    • Lubrication skids
    • Diesel emergency rooms
    • Fuel filters
    • Diping, electrostatic coating or cleaning purposes
    • Gear boxes
    • Drive shafts
    • Engine drive generators
    • Chemical processes
    • Flammable or combustible liquid pumps piping or
       containers under pressure such as may be used with
       hydraulic pumping equipment


Approvals

  • NFPA 750
  • FM Approval
 
 


 

Atlanta, GA | Bloomington, IL | Bridgewater, NJ | Chicago, IL | Cincinnati, OH | Raleigh - Durham, NC | Indianapolis, IN | Los Angeles, CA | Kansas City, MO | Las Vegas, NV | Louisville, KY | San Francisco, CA | St. Louis, MO | Tampa, FL | Battle Creek, MI | Brooklyn, NY | Cherry Hill, NJ | Columbus, OH | Dallas, TX | Fayetteville, NC | Ft. Lauderdale, FL | Ft. Meyers, FL | Ft. Walton Beach, FL | Jacksonville, FL | Lafayette, LA | Morristown, TN | Nashville, TN | Newport, NC | New York, NY | Orlando, FL | Pittsburgh, PA | Tallahassee, FL
Fire Alarm Systems
Fire Alarm Testing
Fire Alarm Training
Fire Alarm Inspection
Conventional Fire Alarm
Intelligent Fire Alarm
Fire Alarm Monitoring
Fire Detection Systems
Fire Detection Devices
Flame Detection
Smoke Detection
Air Sampling
Spot Heat Detection
Video Smoke Detection
Linear Heat Detection
Gas Detection
Fire Notification Systems
Fire Notification Service
Fire Alarm Notification
Audiovisual Notification
Mass Notification
Exit Point Notification
Voice Evacuation Notification
Water Mist Fire Suppression
Marioff Hi Fog Fire Suppression
Micromist Fire Suppression
Water Mist Fire Protection
Explosion Protection
Industrial Explosion Protection
Explosion Suppression System Design
Fire Suppression Systems
Halon Fire Suppression
FM 200 Fire Suppression
Data Center Fire Suppression
Sapphire Fire Suppression
Clean Agent Fire Suppression
CO2 Fire Suppression System
Inergen Fire Suppression
Foam Fire Suppression
Water Mist Fire Suppression
Dry Fire Suppression Systems
Server Room Fire Suppression System
Fire Suppression Inspection
Ecaro 25 Fire Suppression
Fire Trace Suppression System
Argonite Fire Suppression
Novec 1230 Fire Suppression
Pro-­Inert Fire Suppression
In Cabinet Fire Suppression
24 Hour Emergency Fire Service
Fire Extinguisher Service
Fire Extinguisher Inspection
Fire Extinguisher Maintenance
Fire Extinguisher Testing
Fire Alarm Service
Fire Alarm Testing
Fire Sprinkler System Repair
Fire Suppression System Recharge
Room Integrity Fan Test
Fire Alarm Monitoring Services
Fire Alarm Training
Fire Systems Training
Fire Protection Design
Fire Alarm System Design
Fire System Installation
Fire Sprinkler Installation
Fire System Modification
Fire System Decommissioning
Ansul
Chemguard
Chemetron
Det-­tronics
Fenwal
Fike
Firetrace
Gamewell-­FCI
Hochiki
Kidde
Marioff
Notifier
Protectowire
RKI
South-­Tek Systems
Xtralis
NFPA Links
NFPA 72 Updates
Copyright © 2009 www.orrprotection.com